Description
Mini sized intelligent controller and applicable
to the compressor of one HP.
Technical Data
Range of temperature displayed : -45~150℃
Range of set temperature:-45~50℃
Accuracy:±1℃
Temperature sensor:NTC, two sensors(Cold-room, defrost control),2m(L)
Compressor: N.O. 30A/250VAC
(applicable to one HP Compressor, if more it needs to connect an AC contactor)
Defrost: N.O. 10A/250VAC
Evap. Fan: N.O. 8A/250VAC
Dimensions:181(Length)×41(Width)×68(Depth)mm
Mounting hole dimensions:138(Length)×32.5(Width)mm
Parameters
Paramete |
Function |
Set range |
Default |
E1 |
Lower setpoint limit |
-45℃~Set temp. |
-30℃ |
E2 |
Higher setpoint limit |
Set temp.~50℃ |
30℃ |
E3 |
Temp.hysteresis |
1~10℃ |
5℃ |
E4 |
Comp.start delay time |
0~10Min |
2Min |
E5 |
Offset on room temp. |
-10~10℃ |
0 |
E6 |
Offset on evap.temp. |
-10~10℃ |
0 |
F0 |
Defrost function |
0=Electric heater 1=Hot gas |
0 |
F1 |
Max.Defrost duration |
1~60Min |
20Min |
F2 |
Defrost interval time |
0~24Hr |
6Hr |
F3 |
Defrost termination temp. |
0~50~0℃ |
8℃ |
F4 |
Display during defrost |
0=Normal display 1 = Last value before defrost |
0 |
F5 |
Dripping time after defrost |
0~10Min |
2Min |
H1 |
Fan start delay time |
0~10Min |
1Min |
H2 |
Fan operating function |
0=Parallel with comp. 1 = Continuous running except defrost |
1 |
H3 |
Fan control during defrosting. |
0=always OFF 1=always ON |
0 |
C2 |
High temperature alarm |
C3~130℃ |
40℃ |
C3 |
Low temperature alarm |
-45℃~C2 |
-40℃ |
C4 |
Alarm time delay |
1~90~1Min |
60Min |