Description
Temperature control
Light control
manual/automatic defrost by turning off
Time/temp. seting to end defrost
Re-start delay
Relay output :1HP(compressor)
Technical Data
Range of temperature displayded:-45℃~45℃
Range of set temperature: -45℃~45℃
Accuracy:±1℃
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Compressor: N.O. 20A/250VAC(one HP)
Light: N.O. 5A/250VAC
Relay output:1HP(compressor)
Parameters
Parameter
|
Function
|
Set range
|
Default
|
E1
|
Lower setpoint limit
|
-45℃~Set temp.
|
-35℃
|
E2
|
Higher setpoint limit
|
Set temp.~45℃
|
20℃
|
E3
|
Temp.hysteresis
|
1~10℃
|
4℃
|
E4
|
Comp.start delay time
|
0~10Min
|
2Min
|
E5
|
Offset on room temp.
|
-5~5℃
|
0℃
|
E6
|
Offset on room temp.
|
-5~5℃
|
0℃
|
F1
|
Max.defrost duration
|
1~60Min
|
20Min
|
F2
|
Defrost interval time
|
0~24Hr
|
6Hr
|
F3
|
Defrost termination temp.
|
0~20℃
|
8℃
|
F4
|
Display during defrost
|
0=Nomal display
1=Last value befroe defrost |
0
|