Features
Temperature Control / Evap. Fan Control
Manual, automatic defrost by electric heater / hot gas
Time、temperature setting to end defrosting
High、low temperature alarm
Condenser high temperature alarm
Value Storing / Self Testing
Technical Data
Range of temperature displayed : —45~150℃ (-45~302℉)
Range of set temperature: —45~100℃ (-45~212℉)
Accuracy:±1℃ (±2℉)
Compressor: N.O. 30A/250VAC
Defrost: N.O. 10A/250VAC
Evap.Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×70(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Paramete
|
Function
|
Set range
|
Default
|
E1
|
Lower setpoint limit
|
-45℃/-45℉~Set temp.
|
-35℃/-31℉
|
E2
|
Higher setpoint limit
|
Set temp.~100℃/212℉
|
20℃/68℉
|
E3
|
Temp.hysteresis
|
1~20℃/1~36℉
|
4℃/7℉
|
E4
|
Comp.start delay time
|
0~10Min
|
2Min
|
E5
|
Offset on room temp.
|
-20~20℃/-36~36℉
|
0
|
E6
|
Offset on evap.temp.
|
-20~20℃/-36~36℉
|
0
|
E7
|
Offset on condens
|
-20~20℃/-36~36℉
|
0
|
F0
|
Defrost function
|
0=Electric heater
1=Hot gas |
0
|
F1
|
Max.Defrost duration
|
1~60Min
|
20Min
|
F2
|
Defrost interval time
|
0~24Hr
|
4Hr
|
F3
|
Defrost termination temp.
|
0~30℃/32~86℉
|
8℃/46℉
|
F4
|
Display during defrost
|
0=Normal display
1=Last value before defrost |
0
|
F5
|
Fan operating function
|
0=Parallel with comp.
1=Continuous running except defrost
|
0
|
C1
|
Temperature unit
|
℃=Celsius ℉=Fahr.
|
℃
|
C2
|
High temperature alarm
|
C3~100℃/212℉
|
40℃/104℉
|
C3
|
Low temperature alarm
|
-45℃/-45℉~C2
|
-40℃/-40℉
|
C4
|
Alarm delay time
|
1~90Min
|
60Min
|
C5
|
Condenser high temperature alarm value
|
0~120℃/0~248℉
|
80℃/176℉
|