SF-104P SHANGFANG Digital Temperature Controller SF-104-P -45 to 150 degree

(No reviews yet) Write a Review
SKU:
HGTZ-DYAL-6TLP
MPN:
SF-108
Weight:
0.50 KGS
  • SF-104P SHANGFANG Digital Temperature Controller SF-104-P -45 to 150 degree
  • SF-104P SHANGFANG Digital Temperature Controller SF-104-P -45 to 150 degree
  • SF-104P SHANGFANG Digital Temperature Controller SF-104-P -45 to 150 degree
US $45.00

Description

Detailed Description

 

1.Ideal or fan cooling freezers & cold rooms of low temperature

2. With password function

3.Waterproof panel

4.Evaporator fan control

5.Time/Temp setting to end defrosting

6.Automatically, manually defrost by electric heater

7.Re-start delay / Parameter locking

8.Celsiuc/Fahrenheit degree selection

9.Renew factory defaults by button operation

10.Range:-45 to 150 degree C (-45 to 150 degree F)

11.Accuracy: ±1 degree C (±2 degree F)

12.Power supply: 230VAC or 120VAC , 50/60Hz

13.Compressor:20A/1HP

14.Heater:10A/250VAC

15.Evap.fan:5A/250VAC

16.Sensor:NTC, 2pcs (room temperature & defrosting control)

17.Dimension: 77(L)×35(W)×60(D)mm

18.Mounting hole dimension:71(L)×29(W)mm

Code

 Function

Set Range

 Default

PAS

Password

00 to 99

 

E1

Lower setpoint limit

-45oC/oF to Set temp.

-22oC/-8oF

E2

Higher setpoint limit

Set temp. to 45oC/120oF

10oC/50oF

E3

Temp. hysteresis

1 to 20oC/1 to 36oCF

5oC/9oF

E4

Compressor start delay time

0 to 10 Min

2 Min

E5

Offset on room temp.

-20 to 20oC/oF

0

E6

Offset on evap. temp

-20 to 20oC/oF

0

F1

Max. defrost duration

1 to 60 Min

20 Min

F2

Defrost interval time

0 to 24 Hr

4 Hr

F3

Defrost termination temp.

0 to 30oC/32 to 86oF

12oC/54oF

F4

Display during defrost

0=Normal display
1=Last value before defrost

1

F5

Fan operating function

0=Paraller with comp.1=Continuous running(except defrost)2=Controlled by F9

0

F6

Dripping time

0 to 10 Min

2Min

F7

Fan start delay mode after defrost

0=time   1=Controlled by F9

1

F8

Fan start delay time after defrost

0 to 10 Min

2 Min

F9

Fan start temp. (Defrost sensor temp.)

-30 to 30oC/-22 to 86oF

-4oC/25oF

C1

Temperature unit

oC=Celsius oF =Fahrenheit

0

C2

High temperature alarm

Set value to 49oC/121oF to OFF

40oC/104oF

C3

Low temperature alarm

OFF to -44oC/oF

OFF

C4

Alarm time delay

0 to 90 Min

30Min

 

 

View AllClose