Description
Temperature Control
Evaporator fan control/Light control
Manual/automatic defrost by electric heater
Time/temp.Setting to end defrost
Re-start delay
Celsius/Fahrenheit degrees
Technical Data
Range of temperature displayed : -45~100℃(-45~120℉)
Range of set temperature: -45~45℃ (-45~120℉)
Accuracy:±1℃
Compressor: N.O. 20A/250VAC
Light: N.O. 5A/250VAC
Defrost: N.O. 10A/250V
Evap.Fan: N.O. 5A/250VAC
Dimension:190(Length)×70(Width)×60(Depth)mm
Mounting hole dimension:171(Length)×58(Width)mm
Parameters
Parameter
|
Function
|
Set range
|
Default
|
E1
|
Lower setpoint limit
|
-45℃/-40℉~Set temp.
|
-35℃/-31℉
|
E2
|
Higher setpoint limit
|
Set temp.~45℃/120℉
|
45℃/120℉
|
E3
|
Temp.hysteresis
|
1~20℃/1~36℉
|
4℃/7℉
|
E4
|
Comp.start delay time
|
0~10Min
|
2Min
|
E5
|
Offset on room temp.
|
-20~20℃/℉
|
0
|
E6
|
Offset on evap.temp
|
-20~20℃/℉
|
0
|
C1
|
Temperature unnit
|
0=℃ 1=℉
|
0
|
F1
|
Max.defrost duration
|
1~60Min
|
20Min
|
F2
|
Defrost interval time
|
0~24Hr
|
6Hr
|
F3
|
Defrost termination temp.
|
0~30℃/32~86℉
|
8℃/46℉
|
F4
|
Display during defrost
|
0=Normal display
1=Last value before defrost
|
0
|
F5
|
Fan operating function
|
0=Paraller with comp.
1=Continuous running except defrost
|
0
|
F6
|
Dripping time
|
1~10Min
|
2Min
|
F7
|
Fan start delay mode after defrosting
|
0=Temperature 1=Time
|
1
|
F8
|
Fan start delay time after defrosting
|
1~10Min
|
2Min
|
F9
|
Fan start delay temp.after defrosting
|
-30~30℃/-22~86℉
|
5℃/41℉
|